Short circuit

(Redirected from Electrical faults)
Jump to navigation Jump to search
File:Crossed wires.JPG
Tree limbs cause a short circuit during a storm

A short circuit (sometimes abbreviated to short or s/c) in an electrical circuit allows a current along a different path from the one intended. The electrical opposite of a short circuit is an "open circuit", which is an infinite resistance between two nodes. It is common to misuse "short circuit" to describe any electrical malfunction, regardless of the actual problem.

Definition

A short circuit is an abnormal low-resistance connection between two nodes of an electrical circuit that are meant to be at different voltages. This results in an excessive electric current (overcurrent) limited only by the Thevenin equivalent resistance of the rest of the network and potentially causes circuit damage, overheating, fire or explosion. Although usually the result of a fault, there are cases where short circuits are caused intentionally, for example, for the purpose of voltage-sensing crowbar circuit protectors.

In circuit analysis, the term short circuit is used by analogy to designate a zero-impedance connection between two nodes. This forces the two nodes to be at the same voltage. In an ideal short circuit, this means there is no resistance and no voltage drop across the short. In simple circuit analysis, wires are considered to be shorts. In real circuits, the result is a connection of nearly zero impedance, and almost no resistance. In such a case, the current drawn is limited by the rest of the circuit.

Examples

A short circuit is to connect the positive and negative terminals of a battery together with a low-resistance conductor, like a wire. With low resistance in the connection, a high current exists, causing the cell to deliver a large amount of energy in a short time.

In electrical devices, unintentional short circuits are usually caused when a wire's insulation breaks down, or when another conducting material is introduced, allowing charge to flow along a different path than the one intended.

A large current through a battery (also called a cell) can cause the rapid buildup of heat, potentially resulting in an explosion or the release of hydrogen gas and electrolyte, which can burn tissue and may be either an acid or a base. Overloaded wires can also overheat, sometimes causing damage to the wire's insulation, or a fire. High current conditions may also occur with electric motor loads under stalled conditions, such as when the impeller of an electrically driven pump is jammed by debris; this is not a short, though it may have some similar effects.

In mains circuits, short circuits are most likely to occur between two phases, between a phase and neutral or between a phase and earth (ground). Such short circuits are likely to result in a very high current and therefore quickly trigger an overcurrent protection device. However, it is possible for short circuits to arise between neutral and earth conductors, and between two conductors of the same phase. Such short circuits can be dangerous, particularly as they may not immediately result in a large current and are therefore less likely to be detected. Possible effects include unexpected energisation of a circuit presumed to be isolated. To help reduce the negative effects of short circuits, power distribution transformers are deliberately designed to have a certain amount of leakage reactance. The leakage reactance (usually about 5 to 10% of the full load impedance) helps limit both the magnitude and rate of rise of the fault current.

Damage

Damage from short circuits can be reduced or prevented by employing fuses, circuit breakers, or other overload protection, which disconnect the power in reaction to excessive current. Overload protection must be chosen according to the maximum prospective short circuit current in a circuit. For example, large home appliances (such as clothes dryers) typically draw 10 to 20 amperes, so it is common for them to be protected by 20–30 ampere circuit breakers, whereas lighting circuits typically draw less than 10 amperes and are protected by 15–20 ampere breakers. Wire gauges are specified in building and electrical codes, and must be carefully chosen for their specific application to ensure safe operation in conjunction with the overload protection.

See also

Template:Portalpar

External links

ar:دائرة قصر ca:Curtcircuit cs:Zkrat de:Elektrischer Kurzschluss et:Lühis eo:Kurta cirkvito id:Hubungan pendek is:Skammhlaup it:Cortocircuito he:קצר חשמלי lt:Trumpasis jungimas hu:Rövidzárlat ms:Litar pintas nl:Kortsluiting no:Kortslutning sk:Skrat fi:Oikosulku sv:Kortslutning uk:Коротке замикання